RF-50H Live-line Gas Purification System
Online Purification • Circulation Replacement • Dynamic Monitoring
Particulate Treatment: ≤1 μm
Decomposition Byproduct Treatment: Adsorption type
Gas Replacement Pressure Fluctuation: 0.01 MPa
Vacuum Pumping Rate: 17 m³/h
Annual Leakage Rate: <0.5%
Ultimate Vacuum: ≤10 Pa
Product Introduction
The RF-50H non-stop breathing gas purification and treatment device adopts a unique purification method to conduct on-line treatment of the gas in the gas chamber of high-voltage electrical equipment. It can simultaneously treat impurities such as micro-water, decomposed product gases, and dust particles in the gas. While ensuring the safe operation of electrical equipment, it conducts continuous breathing, on-line purification, cyclic replacement, and dynamic monitoring of the internal gas. After on-line purification treatment, the gas quality of electrical equipment is improved, ensuring the safe operation of power equipment. Currently, the treatment method of this equipment has been written into the T/CEC 424—2020 “Code of Practice for On-site Treatment of Excessive Humidity in SF6 Inflated Equipment” standard.
Main Features
1. Dry and replace gas under live working conditions, without the need to handle power outage procedures.
2. The unique purification technology of the RF-50H non-stop breathing gas purification and treatment device effectively treats moisture, harmful substances, and particles in the gas.
3. Conduct quality inspection of the SF6 gas in high-voltage switches.
4. The RF-50H non-stop breathing gas purification and treatment device evacuates and detects the vacuum degree of the device’s own system and external pipelines.
5. Conduct double real-time detection and protection of the pressure in the gas chamber to ensure that the pressure in the gas chamber remains within the normal range during the purification process.
6. The charging and discharging operation switching of the RF-50H non-stop breathing gas purification and treatment device is automatically controlled by pressure, breathing and replacing gas intermittently, and operating continuously in a cycle.
7. High-voltage switches have single-interface and double-interface options, different working modes can be selected, controlled by PLC, operated by touch screen buttons, with simple operation.
Product Parameters
Parameter Name |
Parameter Value |
Moisture Removal Efficiency |
1000ppm → 500ppm/50kg gas (24h) 1000ppm → 250ppm/10kg gas (24h) |
Particle Treatment |
≤1 μm |
Decomposition Product Treatment |
Adsorption |
Gas Replacement Pressure Fluctuation |
0.01 MPa |
Vacuum Pumping Speed |
17 m³/h |
Annual Leakage Rate |
<0.5% |
Ultimate Vacuum |
≤10 Pa |
Power Supply |
3-Phase 5-Wire, AC380V, 50Hz |
Weight |
900 kg |
Dimensions |
1400×950×1970 mm (L×W×H) |